Model | 3.6KVA | 6KVA | 8KKVA | 10KVA |
---|---|---|---|---|
Input / voltage (V) | 230V | 230V | 230V | 230V |
Input / current (A) batteries are in charged condition | 21A | 35A | 49A | 61A |
Input / required ext. Input MCB (A) | 30A | 50A | 70A | 100A |
Output / voltage (V) | 230V | 230V | 230V | 230V |
Output / power (KVA) | 3.6 | 6 | 8 | 10 |
Output / power (KW) | 2.9 | 4.8 | 6.4 | 8 |
Output / current (A) | 16 | 26 | 35 | 43 |
Output / Efficiency AC-AC @100% load (%) | 85 | 86 | 87 | 87 |
Output / Efficiency AC-AC @50% load (%) | 84 | 85 | 86 | 86 |
Output / full load, heat dissipation (W), 1W=3.4 BTU | 508 | 781 | 956 | 1195 |
Output / inverter efficiency, at 100% load (%) | 95 | 95 | 95 | 95 |
Backup operation / backup (min) 100% load | 8 | 4 | 7 | 5 |
Backup operation / backup (min) 50% load | 25 | 11 | 23 | 16 |
Backup operation / battery recharge time | Approx. 4 hours | Approx. 4 hours | Approx. 4 hours | Approx. 4 hours |
Backup operation / batteries (12VDC each) | Internal 16 x 7 AH | Internal 16 x 7 AH | Internal 16 x 15 AH | Internal 16 x 15 AH |
Backup operation / expected battery life | 5 years | 5 years | 5 years | 5 years |
Physical / size (cm) H | 63 | 63 | 63 | 63 |
Physical / size (cm) W | 24 | 24 | 24 | 24 |
Physical / size (cm) D | 65 | 65 | 65 | 65 |
Physical / weight (kg), W/O batteries | 85 | 95 | 110 | 125 |
Physical / audible noise (dB), at 1.5m distance | 50 | 51 | 54 | 54 |
Specifications
- Input
- Voltage: see table
- Voltage: range: +10%-15%
- Frequency: 47/63Hz
- Power walk-in: 55
- Protection: circuit breaker, RFI filter
- Power factor: 0.8
- Output:
- Voltage: see table, no DC component
- Regulation: +/-1%
- Freq. tracking range: +/-1, +2Hz, selectable
- Slew rate: 1Hz/Sec.
- Overload: 125% 10 min., 150% 30 sec, 1000% 1 cycle
- Load P.F.: 0.8
- Waveform: sinusoidal
- T.H.D: less than 2% (at linear load)
- Crest factor: 3:1
- Protection: overload and short circuit
- Dynamic response on 100% load change: +/-2%
- Transition time: UPS to and from line, less than 0.5msec
- Rejection ratio: more than 100dB
- Environment:
- Ambient temperature, operating: -10 to 40 Celsius; storage: -20 to 60 Celsius
- Relative humidity: 95% max., non condensation
- Altitude: 1500m w/o derating
- EMI suppression: according to EN55022-B
- UPS standard: IEC 146-4
- MTBF: 100,000 hrs., 250,000 hrs. with static switch
Features
- Power solutions for all your needs
- All specifications given are typical and subject to change without notice.
- L. C. D. data:
- Input: voltage
- Output: current & voltage
- Bypass & inverter: voltage, current & frequency
- Battery: voltage
- Temperature: heat-sink
- Real time and accumulated operational time log (events memory)
- Options:
- Maintenance bypass
- Extended battery backup
- Any other voltage or frequency
- Communication options:
- RS232: modem, computer
- Alarm: shutdown systems
- Remote indication panel