1/1 Phase Micro - Controlled On - Line PWM UPS

Product ID: MS

Send Inquiry
Model 3.6KVA 6KVA 8KKVA 10KVA
Input / voltage (V) 230V 230V 230V 230V
Input / current (A) batteries are in charged condition 21A 35A 49A 61A
Input / required ext. Input MCB (A) 30A 50A 70A 100A
Output / voltage (V) 230V 230V 230V 230V
Output / power (KVA) 3.6 6 8 10
Output / power (KW) 2.9 4.8 6.4 8
Output / current (A) 16 26 35 43
Output / Efficiency AC-AC @100% load (%) 85 86 87 87
Output / Efficiency AC-AC @50% load (%) 84 85 86 86
Output / full load, heat dissipation (W), 1W=3.4 BTU 508 781 956 1195
Output / inverter efficiency, at 100% load (%) 95 95 95 95
Backup operation / backup (min) 100% load 8 4 7 5
Backup operation / backup (min) 50% load 25 11 23 16
Backup operation / battery recharge time Approx. 4 hours Approx. 4 hours Approx. 4 hours Approx. 4 hours
Backup operation / batteries (12VDC each) Internal 16 x 7 AH Internal 16 x 7 AH Internal 16 x 15 AH Internal 16 x 15 AH
Backup operation / expected battery life 5 years 5 years 5 years 5 years
Physical / size (cm) H 63 63 63 63
Physical / size (cm) W 24 24 24 24
Physical / size (cm) D 65 65 65 65
Physical / weight (kg), W/O batteries 85 95 110 125
Physical / audible noise (dB), at 1.5m distance 50 51 54 54
Specifications
  • Input
    • Voltage: see table
    • Voltage: range: +10%-15%
    • Frequency: 47/63Hz
    • Power walk-in: 55
    • Protection: circuit breaker, RFI filter
    • Power factor: 0.8
  • Output:
    • Voltage: see table, no DC component
    • Regulation: +/-1%
    • Freq. tracking range: +/-1, +2Hz, selectable
    • Slew rate: 1Hz/Sec.
    • Overload: 125% 10 min., 150% 30 sec, 1000% 1 cycle
    • Load P.F.: 0.8
    • Waveform: sinusoidal
    • T.H.D: less than 2% (at linear load)
    • Crest factor: 3:1
    • Protection: overload and short circuit
    • Dynamic response on 100% load change: +/-2%
    • Transition time: UPS to and from line, less than 0.5msec
    • Rejection ratio: more than 100dB
  • Environment:
    • Ambient temperature, operating: -10 to 40 Celsius; storage: -20 to 60 Celsius
    • Relative humidity: 95% max., non condensation
    • Altitude: 1500m w/o derating
    • EMI suppression: according to EN55022-B
    • UPS standard: IEC 146-4
    • MTBF: 100,000 hrs., 250,000 hrs. with static switch
Features
  • Power solutions for all your needs
  • All specifications given are typical and subject to change without notice.
  • L. C. D. data:
    • Input: voltage
    • Output: current & voltage
    • Bypass & inverter: voltage, current & frequency
    • Battery: voltage
    • Temperature: heat-sink
    • Real time and accumulated operational time log (events memory)
  • Options:
    • Maintenance bypass
    • Extended battery backup
    • Any other voltage or frequency
  • Communication options:
    • RS232: modem, computer
    • Alarm: shutdown systems
    • Remote indication panel

Main Products