The Fire-Lite MS-5UD five zone, and MS-10UD ten zone Fire Alarm Control Panels bring the latest in technology to conventional fire controls. The MS-5UD and MS-10UD are fully programmable via built-in keypad and 80 character LCD display, so you do not need an external programmer. Both panels have a built-in Digital Alarm Communicator Transmitter (DACT) and availability to add optional equipment: Remote annunciator, Relay module, LED Driver module, Transmitter module and Printer interface module.
Features
- Features :
- # Listed to UL Standard 864, 9th edition.
- # Built-in DACT (Digital Alarm Communicator/Transmitter).
- # Style B (Class B) IDC (Initiating Device Circuit)
- – MS-5UD-3 - five IDCs.
- – MS-10UD-7 - ten IDCs.
- # Style Y (Class B) NAC (Notification Appliance Circuit) - special application power
- # MS-5UD-3 - four NACs. – MS-10UD-7 - four NACs.
- # Notification Appliances may be programmed as
- – Silence Inhibit.
- – Auto-Silence.
- – Strobe Synchronization for System Sensor, Wheelock, Gentex, Faraday, or Amseco devices.
- – Selective Silence (horn-strobe mute).
- – Temporal or Steady Signal.
- – Silenceable or Nonsilenceable.
- # Optional CAC-5X Style Z (Class A) Converter Module for NACs and IDCs (2 required for MS-10UD-7).
- # Form-C Relays for Alarm, Trouble and Supervisory - Contact Ratings 2.0 A@ 30 VDC or 30 VAC (resistive).
- # 3.0 A total system current for MS-5UD-3.
- # 7.0 A total system current for MS-10UD-7.
- # Optional Dress Panel DP-51050
- # Optional Trim Ring TR-CE for semi-flush mounting.
- # 24 volt operation.
- # Low AC voltage sense.
- # Alarm Verification.
- # PAS (Positive Alarm Sequence).
- # Automatic battery trickle charger.
- # Up to eight ANN-BUS annunciators:
- – Optional 8 zone Relay Module ANN-RLY.
- – Optional LED Annunciator Module ANN-LED,
- – Optional Remote Annunciator ANN-80.
- – Optional Remote Printer Gateway ANN-S/PG.
- – Optional LED Annunciator Driver ANN-I/O.
- # Optional 4XTMF module (conventional reverse polarity/city box transmitter).
- PROGRAMMING AND SOFTWARE
- # Can be programmed at the panel with no special software or additional equipment.
- # Programmable Make/Break Ratio.
- #
- # Upload/Download (local or remote) of program and data via integral DACT.
- USER INTERFACE
- # Built-in DACT (Digital Alarm Communicator/Transmitter).
- # Integral 80-character LCD display with backlighting and keypad.
- # Real-time clock/calendar with automatic daylight savings adjustments.
- # ANN-BUS for connection to remote annunciators.
- # Audible or silent walk test capabilities.
- # Piezo sounder for alarm, trouble, and supervisory.
- Key Applications
- Small facilities including:
- # Banks
- # Cinemas
- # Food Stores
- # Restaurants
- # Elementary Schools
- # Strip Malls
- # Small Retail Outlet Stores
- # Small Apartment Buildings
- # Dormitories
- # Small Motels
- # Smaller Healthcare Clinics
- # Nursing Homes
- # Retirement or Assisted Living Facilities
Main Products
Home Security Equipment