1. Applications: for the rated voltage (U0/U) 26/35kV power line in transmission
and transformation power.
2. Standard: GB1206-2002 and IEC60502-1997.
3. Operation performance:
(1) No need to preheat if the installing temperature is above 0oC.
(2) Operating Temperature:90oC for continuous normal operation for PVC Sheathed cable.
(3) Max. Permissible temperature at short circuit (within 5 seconds) 250oC.
(4). Min Bending radius when installing:
Single core bending radius: 20(d+D)�5%;
Three core bending radius: 15(d+D)�5%;
D refers to the actual diameter of cable, and d refers to the actual diameter of conductor.
and transformation power.
2. Standard: GB1206-2002 and IEC60502-1997.
3. Operation performance:
(1) No need to preheat if the installing temperature is above 0oC.
(2) Operating Temperature:90oC for continuous normal operation for PVC Sheathed cable.
(3) Max. Permissible temperature at short circuit (within 5 seconds) 250oC.
(4). Min Bending radius when installing:
Single core bending radius: 20(d+D)�5%;
Three core bending radius: 15(d+D)�5%;
D refers to the actual diameter of cable, and d refers to the actual diameter of conductor.