The ambient temperature under installation should not be lower than: -20 oC.
The bending radius of xlpe cable 240mm is recommended as following:
When the diameter of cable is less than 25mm: not less than 4 times of the diameter of cable
When the diameter of cable is not less than 25mm: not less than 6 times of the diameter of cable
When the cable is used in alternative current system, the rated voltage of cable should be at least equal to the rated voltage of system; when xlpe cable 240mm is used in direct current system, the rated voltage of system should not greater than 1.5 times of the rated voltage of the cable.