Products
  • Products
  • Suppliers
  • Categories

KS Cooling Tower

Product ID: KFT

Send Inquiry
Specifications
  • The Basic Design Condition Of KFT Cooling Tower Is:
    • When hot water temp. is 37 Celsius, cold water temp. is 32 Celsius and ambient wet bulb temp. is 27 Celsius, 13 LPM water flow rate is regarded to be one ton.
Features
  • Long-Durability And Light-Weight:
    • Tower body is made out of F.R.P.( fiberglass reinforced plastics) which is free from corrosion, so it is as durable as steel but as light as PVC. What's more, being coated with a special epoxy composed of anti-ultraviolet agent, the tower body is also resistant to the hurt from sunlight.
  • No Rust:
    • All steel parts are treated by H.D.G.(hot dip galvanization), so none will get rusty.
  • Low Noise:
    • With specially designed axial fan and belt reducer, the tower holds in itself strong wind but very low noise. In addition, there is a high quality silence mat above the basin, that will absorb most of the water drop noise.
  • Few Water Loss:
    • The specially designed PVC drift eliminator can produce excellent efficiency at stopping spray, so the carry-over volume can always be kept within 0.005%, and only a slight pressure drop loss will be caused there.
  • No Clog & Pollution:
    • All nozzles are designed to be with special big orifice so they will not get clogged as what were usually used. Moreover, being installed inside the towers, nor will the nozzles accept dirt from environmental pollution.
  • Good Heat-Exchange Efficiency:
    • The film type cellular fill is made of air vacuum forming PVC sheets which are with corrugated surface and are disposed at cross against each other, so it can do very good job in heat rejection.
  • Light Operating Weight:
    • With shape sloping down into water sump, the basin requires less water storage than common square type basins, so the tower will not carry too much weight during operation. The water sump however is at special large size, so it takes no risk of sucking in air.
  • Easy Erection:
    • All tower supports are made of FRP and are body-formed with basin, so it is very easy to erect to tower, no matter there's isolation steel frame or not.
Model (Cell) Heat Duty / Cooling Capacity (kcal/h) Heat Duty / Water Flow Volume (l/min.) Dimension(mm) / L Dimension(mm) / W Dimension(mm) / H Motor (HP* set) Fan (Dia. m/m) Air Flow (M^3/min) Electric Current (Amp * set 220V/380V) Heat (M) Weight / Dry Weight Weight / Operating Weight
80 (80-C1) 312,000 1040 2130 2130 3120 2*1 1500 580 6.2*1 / 3.6*1 3.5 680 1460
100 (100-C1) 390,000 1300 2130 2130 3120 3*1 1500 630 8.6*1 / 5.0*1 3.6 710 1540
125 (125-C1) 487,500 1625 2415 2415 3260 3*1 1800 700 8.6*1 / 5.0*1 3.8 860 1970
150 (150-C1) 585,000 1950 2415 2415 3260 5*1 1800 950 14*1 / 8.1*1 3.9 940 2070
175 (175-C1) 682,500 2275 2415 2415 3450 5*1 1800 950 14*1 / 8.1*1 4 1000 2160
300 (150-C2) 1,170,000 3905 4550 2415 3260 5*2 1800 950*2 14*1 / 8.1*2 3.9 1800 4070
350 (175-C2) 1,365,000 4550 4550 2415 3450 5*2 1800 950*2 14*1 / 8.1*2 4 1880 4210
700 (175-C4) 2,730,000 9100 8820 2415 3450 5*4 1800 950*4 14*1 / 8.1*4 4 3480 8130
200 (200-C1) 780,000 2600 2740 2740 3510 5*1 2100 1100 14*1 / 8.1*1 4.2 1150 2610
225 (225-C1) 877,500 2925 2740 2740 3510 7 2/1*1 2100 1350 20*1 /11.6*1 4.2 1170 2670
250 (250-C1) 975,500 3250 2740 2740 3680 7 2/1*1 2100 1350 20*1 /11.6*1 4.5 1260 2810
400 (200-C2) 1,560,000 5200 5180 2740 3510 5*2 2100 1150*2 14*2 / 8.1*2 4.2 2130 5050
450 (225-C2) 1,755,000 5850 5180 2740 3510 7 2/1*2 2100 1350*2 20*2 /11.6*2 4.2 2230 5240
500 (250-C2) 1,950,000 6500 5180 2740 3680 7 2/1*2 2100 1350*2 20*2 /11.6*2 4.5 2420 5510
600 (200-C3) 2,340,000 7800 7620 2740 3510 5*3 2100 1100*3 14*3 / 8.1*3 4.2 2970 7350
800 (200-C4) 3,120,000 10,400 10,060 2740 3510 5*4 2100 1100*4 14*4 / 8.1*4 4.2 3880 9720
900 (225-C4) 3,510,000 11,700 10,060 2740 3510 7 2/1*4 2100 1350*4 20*4 /11.6*4 4.2 4320 10,350
1000 (250-C4) 3,900,000 13,000 10,060 2740 3680 7 2/1*4 2100 1350*4 20*4 /11.6*4 4.5 4670 10,870
1125 (225-C5) 4,387,500 14,625 12,500 2740 3510 7 2/1*5 2100 1350*5 20*5 /11.6*5 4.2 5520 13,040
1250 (250-C5) 4,875,000 16,250 12,500 2740 3680 7 2/1*5 2100 1350*5 20*5 /11.6*5 4.5 5850 13,610
300 (300-C1) 1,170,000 3900 3350 3350 3930 10*1 2400 1800*1 25*1 /14.5*1 4.3 1590 3600
350 (350-C1) 1,365,000 4550 3350 3350 3930 10*1 2400 1950*1 25*1 /14.5*1 4.5 1750 3750
600 (300-C2) 2,340,000 7800 6400 3350 3930 10*2 2400 1800*2 25*2 /14.5*2 4.3 2600 7000
700 (350-C2) 2,730,000 9100 6400 3350 3930 10*2 2400 1950*2 25*2 /14.5*2 4.5 2950 7300
900 (300-C3) 3,510,000 11,700 9450 3350 3930 10*3 2400 1800*3 25*3 /14.5*3 4.3 3900 10,000
1050 (350-C3) 4,095,000 13,650 9450 3350 3930 10*3 2400 1950*3 25*3 /14.5*3 4.5 4500 10,340
1200 (300-C4) 4,680,000 15,600 12,500 3350 3930 10*4 2400 1800*4 25*4 /14.5*4 4.3 5600 12,600
1400 (350-C4) 5,460,000 18,200 12,500 3350 3930 10*4 2400 1950*4 25*4 /14.5*4 4.5 6100 13,050

Main Products

cooling tower, water pump